JLEZW4-12 Combined Electronic Transformer
Standards
GB/T20840.1、 IEC 61869-1 Instrument Transformer Part 1: General Technical Requirements
GB/T20840.7、 IEC 61869-7 Instrument Transformer Part 7: Electronic Voltage Transformer
GB/T20840.8、 IEC 61869-8 Instrument Transformer Part 8: Electronic Current Transformer
Operation Circumstance
Installation site: Outdoor
Ambient temperature: Min. temperature: -40℃
Max. temperature :+70℃
Average temperature per day ≤ +35℃
Ambient air: There is no obvious dust, smoke, corrosive gas, steam or salt and so on. Altitude: ≤ 1000m
(Please indicate the altitude when the instrument transformers are used in high altitude area.)
Please note when ordering
1. Rated voltage /current ratio.
2. Working princip le.
3. Accuracy classes and rated output.
4. For any other requirement, you can contact us!
Technical Data
Voltage Part | Current Part | |
Rated Ratio | 10kV/ √3/3.25V/ √3/3.25V/ √3/3.25V/ √3/6.5V/3 | 600A/1V/600A/1V/600A/1V/20A/0.2V |
Accuracy Class | 0.5/0.5/0.5/3P | 5P10(0.5S)/5P10(0.5S)/5P10(0.5S)/5P30(1S) |
Rated Secondary Output | 2MΩ/2MΩ/2MΩ/2MΩ | 20kΩ/20kΩ/20kΩ/20kΩ |
Rated Insulation Level | 12/42/75 | 12/42/75 |
Working Princip le | Capacitor divider | Low power coil |