YTJLW10-720-DYH Sealed Pole Type Combined Instrument Transformer
Standards
GB/T20840.1、IEC 61869-1 Instrument Transformer Part 1: General Technical Requirements
GB/T20840.7、IEC 61869-7 Instrument Transformer Part 7: Electronic Voltage Transformer
GB/T20840.8、IEC 61869-8 Instrument Transformer Part 8: Electronic Current Transformer
Operation Circumstance
Installation site: Outdoor
Ambient temperature: Min. temperature: -40℃
Max. temperature :+70℃
Average temperature per day ≤ +35℃
Ambient air: There is no obvious dust, smoke, corrosive gas, steam or salt and so on.
Altitude: ≤ 1000m
(Please indicate the altitude when the instrument transformers are used in high altitude area.)
Please note when ordering
1. Rated voltage /current ratio.
2. Working principle.
3. Accuracy classes and rated output.
4. For any other requirement, you can contact us!
Technical Data
Voltage Part | Current Part | |
Rated Ratio | 10kV/ √3/3.25V/ √3/3.25V/ √3/3.25V/ √3/6.5V/3 | 600A/1V/600A/1V/600A/1V/20A/0.2V |
Accuracy Class | 0.5/0.5/0.5/3P | 5P10(0.5S)/5P10(0.5S)/5P10(0.5S)/5P30(1S) |
Rated Secondary Output | 2MΩ/2MΩ/2MΩ/2MΩ | 20kΩ/20kΩ/20kΩ/20kΩ |
Rated Insulation Level | 12/42/75 | 12/42/75 |
Working Princip le | Capacitor divider | Low power coil |
Schematic Diagram
1. Three phase wiring diagram for voltage part
2. Three phase wiring diagram for current part
3. Wiring princip le for sing le phase sealed pole type combined transformer
4. Secondary wiring diagram for three phase sealed pole